Vent oil Based Poli From Dryer Vent

by mision56
posted 02-07-2017 06:20 PM


3 replies so far

View gwilki's profile

gwilki

300 posts in 1862 days


#1 posted 02-07-2017 10:14 PM

I seriously doubt it. I finish in my basement shop and have a 20” exhaust fan drawing outside air from a window on the opposite wall from the fan. My shop is 12×20, and the smell still gets into the upstairs.

-- Grant Wilkinson, Ottawa ON

View gmakra's profile

gmakra

5 posts in 979 days


#2 posted 02-07-2017 10:56 PM

4 inch duct only moves about 90 CFM.
It sounds like you have about 1200 cubic feet of air in your shop.
You need to think about how many air changes per hour you want to remove the odor.
You will need to factor in make up air to match the air lost.
400 CFM exhaust and make up air will change the air in your shop once every three minutes.

View mision56's profile

mision56

51 posts in 967 days


#3 posted 02-15-2017 03:47 PM



4 inch duct only moves about 90 CFM.
It sounds like you have about 1200 cubic feet of air in your shop.
You need to think about how many air changes per hour you want to remove the odor.
You will need to factor in make up air to match the air lost.
400 CFM exhaust and make up air will change the air in your shop once every three minutes.

- gmakra

Thank you, exactly what I was looking for!