Posted on ELECTRICAL--IN A KITCHEN, can you have an elect. outlet inside a cabinet?

View WhyMe's profile

WhyMe

1376 posts in 2616 days


#1 posted 09-29-2014 08:04 PM

Any outlet that serves counter top space in a kitchen needs to be GFCI protected per the 2011 NEC. Since you plan to leave this outlet accessible to plug in other counter top appliances if needed may make that outlet subject to the GFCI requirement.

- WhyMe

Would this be considered as such? It will be ~33” above the countertop… I m all for safety but do they have a 4-outlet GFCI receptacle? Or can I stack 1 above another on the wall? And is the code for countertop area or entire kitchen? I would probably need one behind the stove instead of where it is now. Would a breaker be cheaper or would I do one GFCI and connect the restof the recptacles downline?

- matermark

All I can say is what NEC states. It says outlets installed to serve counter top surfaces in kitchens shall be GFCI protected, there is no distance set in the code. The cheapest way is to have the outlets protected by an upstream GFCI outlet. You can also use a double gang box with 1 GFCI outlet protecting the second outlet.