Posted on Baileigh JP-1686 Three Phase Electrical Question

View TopamaxSurvivor's profile

TopamaxSurvivor

23346 posts in 5017 days


#1 posted 10-20-2021 05:43 AM

My best guess without all the loads and the distance to the main panel is 60 amp and #6 copper or #4 aluminum minimum. The total load and voltage drop needs to be taken into consideration. My best guess at full load amps on the rotary phase converter is about 32 amps x 1.25 = 40 amps.