Posted on Is it possible to run a 2hp Dust Collector and Saw on a single 240v/30amp dryer circuit?

View TopamaxSurvivor's profile

TopamaxSurvivor

22410 posts in 4920 days


#1 posted 03-29-2021 11:17 PM

I could be wrong, but as the circuit is 30A, I would be hesitant to put anything rated less than 30A in the line.

- JonCrafting


That is correct. 20A outlet needs to be protected by a 20A breaker or fuse.

Edit: The only place that overrated fuse protection is allowed is branch circuits with several 15 amp outlets protected by a 20 A breaker. If the 15 amp outlet is on a circuit by itself. it would require 15A protection.

-- Bob in WW ~ "some old things are lovely, warm still with life ... of the forgotten men who made them." - D.H. Lawrence