Posted on 220v options in my garage?

View HorizontalMike's profile

HorizontalMike

7804 posts in 3476 days


#1 posted 09-08-2016 12:58 PM


.....[snip].....
For instance, you can pull a maximum of 10 conductors of 10 gauge THHN for 3/4” EMT. For Schedule 40 PVC (which I happened to use for my install) it is 9. I can say from experience, pulling up to the max gets tough if you have a lot of corners to go through.
http://sparkyjohn.com/pipefill/pipefill.pdf
- limelight

ALSO, whether bending conduit or using PVC please remember:
  • EACH pull of wire, from one box to another, cannot have more than 180 degrees of bends TOTAL… Each pull…
  • And the closer you come to that 180 degree MAX, the harder it gets to pull.
  • Place junction boxes where you know that the total number of bends will exceed 180 degrees.
  • Don’t be tempted to pull wire before you join lengths of pipe/PVC and glue them together afterwards to bypass that 180 Degree max. You will never be able to replace/remove it in the future because it will act as if you had tied a knot in the wire run…

Good luck!

-- HorizontalMike -- "Woodpeckers understand..."